BS 6231 CK 90°C
- REACH
- RoHS
- CE
- CPR Compliant
Application
High temperature, flame retardant cable designed for use in switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers.
Standard
BS6231 Type CK.
Technical Data
Voltage Rating: 600 / 1000V
Temperature Rating : 90°C (105°C for 15,000 hours)
Minimum Bending Radius :
Cable diameter ≤ 8 mm: 4 x outer diameter.
Approx. diameter > 8 to 12 mm: 5 x outer diameter
Approx. diameter > 12 mm: 6 x outer diameter
Test Voltage: 4000V
Construction
Conductor: Conductor Class 5 flexible plain/metal coated stranded according to EN 60228 cl. 5.
Insulation: PVC (Polyvinyl Chloride) TI3 to BS EN 50363-3.
Properties
- PVC self-extinguishing and flame retardant according to EN 60332-1-2.
Cabel Design Parameters
Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink,
12 – grey.
By adding the suffix (in place of ‘c’) for the conductor type required:
0 = Annealed Bare Copper (ABC), 1 = Annealed Tinned Copper (ATC).
Part Numbers | Nominal Cross Sectional Area (Sq. mm) |
Nominal Thickness of Insulation (mm) |
Mean Overall Diameter |
Approx. Cable Weight (kg/km) |
|
Lower Limit (mm) | Upper Limit (mm) | ||||
02060101xx3c | 0.5 | 0.8 | 2.4 | 3.0 | 11 |
02060102xx3c | 0.75 | 0.8 | 2.6 | 3.1 | 14 |
02060103xx3c | 1 | 0.8 | 2.7 | 3.3 | 16 |
02060104xx3c | 1.5 | 0.8 | 3.0 | 3.6 | 21 |
02060105xx3c | 2.5 | 0.8 | 3.4 | 4.1 | 32 |
02060106xx3c | 4 | 0.8 | 3.9 | 4.8 | 46 |
02060107xx3c | 6 | 0.8 | 4.4 | 5.3 | 64 |
02060108xx3c | 10 | 1.0 | 5.7 | 7.2 | 109 |
02060109xx3c | 16 | 1.0 | 6.7 | 9.0 | 166 |
02060110xx3c | 25 | 1.2 | 8.4 | 11.5 | 256 |
02060111xx3c | 35 | 1.2 | 9.7 | 12.5 | 352 |
02060112xx3c | 50 | 1.4 | 11.5 | 15.4 | 501 |
02060113xx3c | 70 | 1.4 | 13.2 | 17.5 | 692 |
02060114xx3c | 95 | 1.6 | 15.1 | 19.2 | 914 |
02060115xx3c | 120 | 1.6 | 16.7 | 21.2 | 1155 |
02060116xx3c | 150 | 1.8 | 18.6 | 23.9 | 1441 |
02060117xx3c | 185 | 2.0 | 20.6 | 25.9 | 1754 |
02060118xx3c | 240 | 2.2 | 23.5 | 28.9 | 2305 |
Note :
- These cable are also catered with compliance to AWM, UL 1015 and CSA C22.2 No. 210-11 as Trirated cable.
- For current ratings refer table no. 8-1 & 8-2.
*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)