PVC INSULATED BUILDING WIRE

PVC Insulated Building Wire (H07V-R) -6491x

  • REACH
  • RoHS
  • CE
  • CPR Compliant
PVC Insulated Building Wire (H07V-R) -6491x
PVC Insulated Building Wire (H07V-R) -6491x cross

Application

The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts.

Standard

BS EN 50525-2-31. SABS 1507-2, SS 358 Part-3.

Technical Data

Voltage Rating: Uo / U – 450 / 750V

Harmonised Designation: 1.5 mm² to 630 mm² stranded class 2 – H07V-R

Temperature Range: -15°C to 70°C

Minimum Bending Radius:

Upto 10 mm²: 3 X Overall Diameter.

16 & 25 mm²: 4 X Overall Diameter.

Above 25 mm²: 5 X Overall Diameter

Cable Construction

Conductor : Plain annealed copper conductor 1.5 mm² to 630 mm² stranded class 2 complying with BS EN 60228, HD 383, IEC 60228

Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3, HD 21.1, IEC 60227-1, SABS 1411-2

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green / yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.

Part Number Nominal Cross
Sectional Area
(Sq. mm)
Nominal
Insulation
Thickness (mm)
Overall Diameter
Lower Limit
(mm)
Overall Diameter
Upper Limit
(mm)
Approx. Net
Weight (kg/km)
01140101xx10 1.5 0.70 2.70 3.30 19
01140102xx10 2.5 0.80 3.30 4.00 33
01140103xx10 4 0.80 3.80 4.60 50
01140104xx10 6 0.80 4.30 5.20 74
01140105xx10 10 1.00 5.60 6.70 126
01140106xx10 16 1.00 6.40 7.80 184
01140107xx10 25 1.20 8.10 9.70 295
01140108xx10 35 1.20 9.00 10.90 375
01140109xx10 50 1.40 10.60 12.80 510
01140110xx10 70 1.40 12.10 14.60 710
Part Number Nominal Cross
Sectional Area
(Sq. mm)
Nominal
Insulation
Thickness (mm)
Overall Diameter
Lower Limit
(mm)
Overall Diameter
Upper Limit
(mm)
Approx. Net
Weight (kg/km)
01140111xx10 95 1.60 14.10 17.10 950
01140112xx10 120 1.60 15.60 18.80 1240
01140113xx10 150 1.80 17.30 20.90 1530
01140114xx10 185 2.00 19.30 23.30 1800
01140115xx10 240 2.20 22.00 26.60 2500
01140116xx10 300 2.40 24.50 29.60 2990
01140117xx10 400 2.60 27.50 33.20 3860
01140118xx10 500 2.80 30.50 36.90 4900
01140119xx10 630 2.80 34.00 41.10 6370
  • For current ratings refer table no. 10-1 & voltage drop refer table no. 10-2.

*Construction Product Regulation (CPR) is a regulation issued by the European Union with the purpose of regulating the limits of fire resistance and dangerous substances in the materials used in construction. This regulation applies to all products intended to be incorporated, permanently, in construction. Above link provides the DOP (declaration of performance) for the CPR compliance for the product.)