RR KABEL FR-LSH

RR Kabel FR-LSH

  • REACH
  • RoHS
  • CE
RR FR-LSH
RR FR-LSH Cross

FR-LSH (Flame Retardant Low Smoke and Halogen) insulation 70°C | Does not propagate flame & fire | Reduced Smoke and acid gas emission

Application

Flexible single core cable with FR-LSH (Flame Retardant Low Smoke and Halogen) PVC insulation. This cable can be used in panels, cabinets, machines and internal wirings with switchgears, relays, controllers, equipments, controls units, etc. specially in hazard prone areas. They also find their usage in flexible wiring installations in industrial and commercial areas with dense population.

Technical Data

Approvals: IS 694 marked, FIA/TAC

Cable Code: Y (FR-LSH)

Voltage Grade: Up to and including 1100V

Conductor: Flexible electrolytic annealed plain copper, class 5, IS 8130

Insulation: Specially formulated FR-LSH (Flame Retardant Low Smoke and Halogen) PVC, IS 5831

Packing: 200 mtr. In polybag packing or 180 mtr. coil packed in protective cartons

Properties

  • Temperature range: -15°C to +70°C
  • Reduced smoke emission provides higher visibility
  • Minimized acid gas generation
  • Max. short circuit temperature rating: 160°C
  • Self-extinguishing and flame retardant according to IS 10810 P – 61
  • Free from 200+ hazardous substance

Cabel Design Parameters

Kindly complete the part numbers for these cables by adding the suffix (in place of ‘xx’) for the colour required:
01 – green, 02 – black, 03 – red, 04 – blue, 05 – yellow, 06 – green/yellow, 07 – white, 08 – violet, 09 – brown, 10 – orange, 11 – pink, 12 – grey.

Part Number
Nominal Cross
Sectional Area
(sq, mm)
No of Strands/Max. strand dia. (mm) Nominal Insulation Thickness (mm ) Maximum Diameter Over insulation (mm) Max. current carrying capacity (A)
02080101xx50 0.5 16/0.2 0.6 2.6 5
02080102xx50 0.75 24/0.2 0.6 2.8 8
02080103xx50 1 32/0.2 0.6 3.0 13
02080104xx50 1.5 30/0.25 0.7 3.4 17
02080105xx50 2.5 50/0.25 0.8 4.1 24
02080106xx50 4 56/0.30 0.8 4.8 30
02080107xx50 6 84/0.30 0.8 5.3 38
02080108xx50 10 140/0.30 1.0 7.0 52
02080109xx50 16 126/0.40 1.0 8.1 70
02080110xx50 25 196/0.40 1.2 10.2 88
02080111xx50 35 276/0.40 1.2 11.7 112
02080112xx50 50 396/0.40 1.4 13.9 146
02080113xx50 70 360/0.50 1.4 16.0 216
02080114xx50 95 480/0.50 1.6 18.2 262
02080115xx50 120 608/0.50 1.6 20.2 310
02080116xx50 150 750/0.50 1.8 22.5 355
02080117xx50 185 931/0.50 2.0 24.9 415
02080118xx50 240 1200/0.50 2.2 28.4 500
02080119xx50 300 1500/0.50 2.4 31.0 550

Test Parameters

Test Test Method Values
Limited Oxygen Index IS 10810 P-58 > 29%
Limited Temp. Index IS 10810 P-64 ≥ 250 °C
Smoke Density IS 10810 P – 63 < 60 %
Acid Gas Generation IS 10810 P-59 < 20 %
Get a Quote